Nell'odierna industria dei macchinari, quasi tutte le macchine utensili richiedono a trasformatore di controllo. The role of the trasformatore di controllo is often used as the local lighting power supply, signal lamp or indicator power supply for machinery and equipment, and can also be used as the control circuit power supply in electrical equipment. However, when using the trasformatore di controllo, many people may encounter the problem of the trasformatore di controllo being burnt out. In general, what causes the trasformatore di controllo to burn out?
(1) The overloaded use of the trasformatore di controllo transformer causes the temperature rise to be too large, which has exceeded the temperature resistance level of the insulating material, thereby burning the transformer.
(2) L'isolamento tra le spire delle bobine primaria e secondaria è danneggiato o invecchiato, c'è un cortocircuito tra le spire e il surriscaldamento locale porta al burnout.
(3) La parte di saldatura del filo di uscita è una saldatura virtuale e la resistenza di contatto è elevata, determinando un'elevata densità di corrente locale e anche il filo può essere fuso.
(4) Se l'anima di ferro ha bulloni a foro passante, i bulloni devono essere isolati da almeno un lato dell'anima di ferro. In caso contrario, se si verifica un cortocircuito magnetico, i bulloni verranno bruciati in rosso.
The above 4 points are the main reasons why the trasformatore di controllo is prone to burn out! After we understand these 4 factors, when we need to use the trasformatore di controllo, we can avoid the trasformatore di controllo with a little attention. burnt condition.
Response measures to trasformatore di controllo burnout:

(1) For the trasformatore di controllo to be burned out due to overload, it is required to replace a trasformatore di controllo with a larger capacity. The power rating of the applied trasformatore di controllo must be greater than that of the driven appliance.
(2) The cause of the circuit failure causes the short circuit of the low-voltage control circuit, which makes the secondary coil current of the trasformatore di controllo too large, which exceeds the rated current of the transformer and burns the machine tool trasformatore di controllo. In this regard, the current limit insurance can be added in front of the transformer for protection.
(3) It is usually necessary to check the insulation of the line. When the insulation of the trasformatore di controllo is found to be damaged or aged, the transformer should be replaced in time to avoid leakage and short circuit.
(4) Controllare se ci sono inceppamenti nella parte rotante della macchina per evitare sovracorrenti.